PS 10
Measuring ranges from ± 250 Pa to ± 100 kPa.
In addition to differential pressure, the differential-pressure transducer PS 10 also records positive and negative overpressure. The central unit is a pressure cell with a diaphragm spring made of beryllium bronze which, in accordance with the pressure difference, is displaced between two chambers. The displacement is measured, without making contact, via an inductive displacement recorder. The device does not contain any components that can rub against each other or parts subject to mechanical wear. The device is primarily designed as measuring device for applications in air-conditioning and ventilation technology.
|
The 3 or 4-figure LC display is available as an option. In addition to Pa and kPa, it can also display mmWs etc.
An optional time constant of up to 5 s (only pressure transducer) means the device can also be used under fluctuating pressure conditions and generates a stabilised output signal. |
Measuring ranges: from ± 250 Pa to ± 100 kPa Linearity: ± 2 % Output signals: 0-10 V, 0-20 mA, 4-20 mA Supply voltages: 24 VAC, 24 VDC, 230 VAC Medium: air, all non-aggressive gases Further information available on request | |